Explosion Protection for Dust Collection on Biomass

Resource from:  https://www.engineerlive.com Likes:255
Mar 25,2024

4.png

Dust explosions and fires in the biomass industry, including pellet manufacturing sites, are not unusual occurrences.  From hammermills to conveyors, dryers, coolers and storage vessels, typically four of the five elements needed to create an explosion – fuel, oxygen, confinement and dust dispersion – are present during normal operations.  The only missing ingredient for a potentially devastating explosion to occur is an ignition source.  One process vessel most prone to dust explosions is the Air-Material Separator (AMS) which in a pellet plant can be a dust collector/baghouse or cyclone.  

The purpose of the AMS is to separate the fines from the airstream which makes these vessels among the most susceptible to explosions within the entire process.  The driest and finest dust within the process stream is usually found in these vessels and the smaller and drier the particle, the lower the ignition energy required to initiate an event.  Adding to this threat is the smaller the particle size for a given product, the more surface area by volume is available for heat absorption, resulting in a more dynamic explosion with a higher deflagration index (KST). Another significant risk is that many pellet processes use a central dust collector, aspirating off several vessels and conveyors.  An explosion in any section can propagate through the connected ducts to multiple vessels upstream and downstream, causing secondary explosions with devastating results.

For any facility, the first line of defense must be prevention.  This should include many of the following practices:

Proper grounding and bonding for static control

Magnetic separators or other means to identify and remove tramp metal

Bearing temperature monitoring or linear heat detection

Electrical equipment rated for the hazard area

Housekeeping to minimize residual dust buildup

Spark detection and suppression on conveyors and dust lines

Hazardous awareness training

A Dust Hazard Analysis should be conducted to identify areas of risk within the facility and suggest strategies to minimize the potential for an explosion during normal operating and upset conditions.  Because abnormal conditions can happen, ATEX compliance requires that the AMS be equipped with explosion protection.  The most common forms of protection found in biomass plants are explosion venting, flameless venting, suppression and isolation.

Explosion vents are panels that are strategically located on the sides of the baghouse, or on top of the cyclone.  These panels rupture from the deflagration pressures, creating an opening which will release the fireball plus burnt and unburnt dust. Venting is designed to reduce the pressure build up within the protected vessel (PRED) below that which would cause vessel rupture.  Typical vent styles are; Flat vents which are typical for baghouses that operate at ambient to -20” wg and domed vents which are an option for pressure-cycling vessels like dust collectors, or for higher-vacuum applications.  When considering explosion vents, the most important factor must be whether the vented fireball can be directed to a safe outside area where no equipment, buildings or personnel may be present.  The fireball from a vented explosion can eject 15m or more.    

Flameless venting combines an explosion relief vent or valve with a flame arrestor material. The vent or valve installed on the process vessel, opens during a deflagration. But unlike a standard relief vent, the flame and most of the heat from the deflagration is absorbed by the flame arrestor, with the deflagration overpressure discharged outside the vessel. Note that a safety perimeter must still be established around the flameless vent or valve to protect workers from the thermal discharge.

An Explosion suppression system detects the incipient deflagration and, within milliseconds, injects a dry chemical extinguishing agent into the protected vessel to suppress the explosion before damaging pressure buildup can occur. These systems typically use pressure sensors and/or optical flame detectors as the detection means. Static detectors with a set pressure setting have been commonly used in the past but Rate of Pressure Rise detectors are becoming much more prevalent due to their high immunity against inadvertent operation from normal operating pressure fluctuations.

Regardless of the protection solution used, flame propagation to connected vessels remains a high threat unless explosion isolation is installed.  Passive solutions can include a rotary gate valve that meets ATEX compliance or a flap-style isolation valve on the AMS inlet.  Flap valves are closed by the pressure wave preceding the flame propagating through the duct, to prevent the fireball from moving further upstream. Care must be taken when considering flap-style isolation valves to ensure that the valve is designed and approved for the specific application.  Some limitations include KST, minimum and maximum allowable distance from the vessel, maximum PRED allowable, and minimum ignition temperature (MIT) of the dust.  

Two active explosion isolation techniques are also options. Chemical explosion isolation is typically used in conjunction with explosion suppression systems, or on vessels equipped with explosion venting where flap valves cannot be employed, such as on vertical ducts.  High-speed gate valves can also be used for isolation, although because of their cost, these valves are less frequently employed in biomass plants than other isolation techniques.

While the AMS is critical to maintain good housekeeping and reducing the risk of a secondary explosion inside the facility, it is one of the most susceptible vessels to an explosion at the plant.  Developing sound explosion prevention strategies, combined with suitable explosion protection, will help limit the explosion risk to operators and the facility.


(https://www.engineerlive.com)
【CBCC News Statement】
1.The news above mentioned with detailed source are from internet.We are trying our best to assure they are accurate ,timely and safe so as to let bearing users and sellers read more related info.However, it doesn't mean we agree with any point of view referred in above contents and we are not responsible for the authenticity. If you want to publish the news,please note the source and you will be legally responsible for the news published.
2.All news edited and translated by us are specially noted the source"CBCC".
3.For investors,please be cautious for all news.We don't bear any damage brought by late and inaccurate news.
4.If the news we published involves copyright of yours,just let us know.

BRIEF INTRODUCTION

Cnbearing is the No.1 bearing inquiry system and information service in China, dedicated to helping all bearing users and sellers throughout the world.

Cnbearing is supported by China National Bearing Industry Association, whose operation online is charged by China Bearing Unisun Tech. Co., Ltd.

China Bearing Unisun Tech. Co., Ltd owns all the rights. Since 2000, over 3,000 companies have been registered and enjoyed the company' s complete skillful service, which ranking many aspects in bearing industry at home and abroad with the most authority practical devices in China.